STR4/8 Hardware Manual
920-0030J
5/12/2015
current that will be applied to the motor: SW1 and SW2. Please set them according to the
illustration below.
Step 3: Seing Idle Current
Motor heating and power consumption can also be reduced by lowering the motor current
when it is not moving. e STR will automatically lower the motor current when it is idle to
either 50% or 90% of the running current. e 50% idle current seing will lower the holding
torque to 50%, which is enough to prevent the load from moving in most applications. is
reduces motor heating by 75%. In some applications, such as those supporting a vertical load, it
is necessary to provide a high holding torque. In such cases, the idle current can be set to 90%
as shown below.
12
100%
12
90%
12
80%
12
70%
4
50%
4
90%
Vista de página 18