CANopen User Manual
Appendix F - Homing Methods
Set Running Parameters
Set the homing and index velocities, acceleration/deceleration, offset and home sensor (if
required) using OD entries 6099
h
, 609A
h
, 607C
h
, and 7001
h
respectively.
Note: It is important that the limit switch settings have been dened in ST Congurator or
Quick Tuner prior to using the CANopen Homing Mode.
Enable Homing Mode
To enable Homing Mode, the value 0006
h
must be written to the mode of operation OD entry,
located at dictionary address 6060
h
. The mode of operation can be veried using OD 6061
h
- mode
of operation display - which is updated when the current operation mode is accepted.
After power up or node reset, the drive is in disabled state. The value 0006
h
must be written
to the control word OD entry, located at dictionary address 6040
h
. This will put the drive into “ready
to switch on” state and is ready to enable drive operation. If the value 0006
h
is not written to the
control word rst, the drive operation can not be enabled.
To put the drive into Operation Enabled Mode, write 000F
h
to the controlword OD entry,
located at dictionary address 6040
h
.
Starting the Homing Procedure
Set the Homing Method required using OD entry 6098
h
. To start the homing procedure, bit 4
of the controlword OD entry located at dictionary address 6040
h
, must transition from 0 to 1. The
status of the homing procedure can be monitored using the statusword OD entry 6041
h
.
Homing Method Diagrams
Homing Method 1
Homes to the rst index CCW after the CW limit switch is reached.